Voltage Drop Calculator

Calculate voltage drop percentage and find the correct wire gauge for any circuit. Enter load current, run length, and conductor type for an instant NEC 3% drop compliance check.

Circuit Basics

Load and Distance

Enter the one-way distance from breaker panel to the load. The formula already accounts for the return path.

Conductor

Conductor Material
Voltage Drop
5.93 V
Drop Percentage
4.94%
Load Voltage
114.1 V
Recommended Gauge
12 AWG
NEC Voltage Drop Check
Fail: Branch circuit drop 4.94% - recommended max 3%.
Pass: Combined feeder + branch recommended max 5%.
Pass: 12 AWG copper rated for 20A - your load is 20.0A.
Run length: 75 ft
Formula constant K: 12.9 (copper)
Phase multiplier: 2.000
Circular mils used: 6,530 CM
Managing multiple electrical jobs?
Jobber helps electrical contractors quote, schedule, and invoice clients in one place.
Try Jobber Free ->

Affiliate link - we may earn a commission at no cost to you.

Need a multimeter, wire strippers, or conduit tools?
Shop professional electrical tools and testing equipment on Amazon.
Shop on Amazon ->

Affiliate link - we may earn a commission at no cost to you.

How to Use the Voltage Drop Calculator

Start with the circuit basics. Choose the system voltage that matches the equipment nameplate or panel voltage, then choose single-phase or three-phase. Single-phase branch circuits use the full round-trip path in the voltage drop formula, while three-phase circuits use the 1.732 multiplier. Next, enter the load current in amps. Use the actual expected running load when checking voltage drop, not only the breaker size, unless you are doing an early planning estimate.

InputWhat it controlsField note
System voltageDrop percentage and load voltageUse the equipment or panel voltage
Circuit phaseFormula multiplierSingle-phase uses 2; three-phase uses 1.732
Load currentVoltage drop amountEnter running amps or design load
One-way run lengthConductor distanceDo not enter round-trip length
Wire gauge and materialResistance and ampacityCopper and aluminum use different K values

The Find Minimum Wire Size toggle is useful when you are designing a new run and want the smallest AWG that keeps branch circuit drop at or below 3%. Leave it off when you are checking an existing conductor size. The NEC panel then separates three checks: branch circuit voltage drop, combined 5% guidance, and conductor ampacity. That separation matters because a wire can pass voltage drop at a short distance while still being too small for the amperage.

Note
Voltage drop is a design check, not a replacement for a licensed electrician, the NEC, or your local AHJ. Always verify conductor insulation temperature, termination ratings, conduit fill, derating, and breaker compatibility before installation.

How to Calculate Voltage Drop

Voltage drop is the voltage lost as current flows through the resistance of the conductor. Longer runs, higher current, smaller wire, and aluminum conductors all increase the drop. SpecMath uses the standard circular mil formula with K equal to 12.9 for copper and 21.2 for aluminum. The length entered is one-way from the source to the load because the single-phase multiplier already accounts for the return path.

Formula
Single-phase voltage drop = (2 x K x I x L) / CM Three-phase voltage drop = (1.732 x K x I x L) / CM Drop percentage = voltage drop / source voltage x 100 Load voltage = source voltage - voltage drop
Worked exampleCalculationResult
12 AWG copper(2 x 12.9 x 20A x 75 ft) / 6,530 CM5.93 volts
Percentage on 120V5.93 / 120 x 1004.94% - fails 3% guidance
10 AWG copper(2 x 12.9 x 20A x 75 ft) / 10,380 CM3.73 volts, 3.11%
8 AWG copper(2 x 12.9 x 20A x 75 ft) / 16,510 CM2.34 volts, 1.95%

That example shows why long 120V circuits can need a larger conductor even when the breaker ampacity looks acceptable. A 20 amp circuit on 12 AWG copper may be legal by ampacity, but the load at the far end can still receive too little voltage for good performance.

AWG Wire Gauge Reference Table

American Wire Gauge sizes get larger as the number gets smaller. Circular mil area is what the voltage drop formula uses, because conductor area directly affects resistance. The ampacity values below are copper values from the 75 degree C column style used for many equipment terminations; aluminum is estimated at 80% of the equivalent copper value in the calculator.

AWG SizeCircular MilsCopper Ampacity (75C)Common Use
14 AWG4,11015ALight circuits, outlets
12 AWG6,53020AKitchen, bath, garage outlets
10 AWG10,38030ADryers, AC units, water heaters
8 AWG16,51050ARanges, large AC, subpanels
6 AWG26,24065ASubpanels, EV chargers
4 AWG41,74085AService entrance, large subpanels
2 AWG66,360115AService entrance
1/0 AWG105,600150AMain feeders
2/0 AWG133,100175AMain feeders
3/0 AWG167,800200A200A service
4/0 AWG211,600230A200A+ service
Note
Ampacity depends on conductor insulation, terminal temperature rating, conduit fill, ambient temperature, number of current-carrying conductors, and local code. Always verify against NEC Table 310.16 and the local authority having jurisdiction before buying material.

When to Upsize Your Wire - Practical Rules

Wire upsizing is not only about passing inspection. It protects equipment, reduces wasted energy, and keeps motors, compressors, lighting, and electronics operating closer to their intended voltage. A circuit that is technically protected by the breaker can still perform poorly if the run is long enough.

  • Upsize when the run exceeds 50 feet on a 15A or 20A branch circuit, especially at 120 volts.
  • Upsize when the run exceeds 100 feet on any circuit, regardless of amperage, before finalizing the design.
  • Upsize motor loads because starting current can run 6 to 8 times higher than running current.
  • Upsize continuous loads that run 3 or more hours because NEC load sizing often uses 125% of continuous load.
  • Treat aluminum differently from copper and verify every termination is rated for the conductor material.

For detached garages, sheds, outbuildings, pools, pumps, and long landscape lighting runs, it may be cheaper and cleaner to install a larger feeder to a small subpanel rather than running several long branch circuits from the main panel.

Common Voltage Drop Mistakes

Voltage drop mistakes usually come from treating breaker size as the whole design. Breaker size protects the conductor from overcurrent, but it does not guarantee that the load receives enough voltage at the end of a long run. The farther the equipment is from the panel, the more the calculation matters.

  • Using 12 AWG for a 100-foot garage circuit without checking voltage drop first.
  • Forgetting that feeder drop and branch circuit drop add together along the same circuit path.
  • Sizing wire only to the breaker rating and ignoring conductor length, phase, and material.
  • Skipping temperature and conduit derating when many current-carrying conductors share one raceway.
  • Entering round-trip length even though the formula already accounts for the return conductor on single-phase circuits.
Note
The safest habit is simple: measure one-way distance, enter the actual load, check voltage drop, then check ampacity. Do all four before ordering wire.

Professional Tips for Long Wire Runs

Long runs reward planning. If several loads are located far from the main panel, a dedicated feeder and subpanel can reduce material complexity and leave room for future circuits. Aluminum SER or feeder cable may be cost-effective for larger subpanel runs, while copper is often preferred for smaller branch circuits and tighter terminations.

Field strategyWhy contractors use it
Remote subpanelShortens branch circuits and leaves space for future loads
Larger feederOften cleaner than several oversized branch circuits
Parallel conductorsCan be economical on very large long-distance feeders when permitted
Clear labelingHelps future troubleshooting at both the panel and load end

Always plan the full installation, not just the math. Conduit bends, pull boxes, conductor fill, grounding, disconnect requirements, burial depth, wet-location ratings, and equipment nameplates can all change the final material list. The calculator gives the voltage and AWG starting point; the finished job still needs code-compliant installation details.

Voltage Drop Calculator FAQ

What is the maximum voltage drop allowed by the NEC?

The NEC recommends no more than 3% voltage drop for branch circuits and no more than 5% combined for feeders and branch circuits together. These are recommendations in the NEC informational notes, not hard requirements, but most electricians, engineers, and inspectors treat them as the practical standard.

What wire gauge should I use for a 100-foot run at 20 amps?

For a 100-foot, 20-amp copper circuit on 120 volts, 10 AWG keeps voltage drop near the practical limit and 8 AWG gives a more comfortable margin. Using 12 AWG at this distance creates excessive voltage drop for many branch circuits. Use the SpecMath Voltage Drop Calculator to verify your exact run length, phase, material, and load.

How do I calculate voltage drop for a three-phase circuit?

Use the formula: voltage drop equals 1.732 multiplied by the resistivity constant K, the load current, and the one-way run length, divided by the circular mils of the conductor. The 1.732 multiplier replaces the factor of 2 used in single-phase calculations because three-phase power is balanced across three conductors.

Is aluminum wire safe for residential electrical wiring?

Aluminum wire is safe and code-compliant for service entrance conductors and larger feeders when it is installed with approved terminations. It is not usually preferred for small residential branch circuits because it expands and contracts more than copper. When aluminum is used, verify CO/ALR or aluminum-rated terminals and follow local code requirements.

Why does voltage drop matter for motors and HVAC equipment?

Motors and HVAC compressors running on undersized wire receive lower voltage than rated, which causes higher current draw and extra heat. That heat can shorten motor life, increase nuisance trips, and reduce equipment performance. Always size wire for motor circuits using both ampacity and voltage drop, not breaker size alone.